| EU-Model | 10kW 16kWh | 12kW 16kWh | |
|---|---|---|---|
| AC Input | Rated Input Voltage (VAC) | 220 / 230 / 240; L + N + PE | |
| Voltage Range (VAC) | 90–280±3 (normal mode); 170–280±3 (UPS mode) | ||
| Frequency (Hz) | 50/60 (Auto detection) | ||
| AC Output | Rated Capacity (W) | 10000W | 12000W |
| Surge Power (VA) | 20000VA | 24000VA | |
| Voltage (VAC) | 220 / 230 / 240 | ||
| Power Factor (PF) | 1 | ||
| Frequency | 50/60Hz±0.1% | ||
| Switch Time (ms) | 10 | 10 (APP/UPS mode) 20 (GEN mode) | |
| Wave Form | Pure Sine Wave | ||
| Overload Capacity (Battery Mode) | (105% < load <110%)±5%: report error and turn off the output after 5 minutes; (110% < load <125%)±5%: report error and turn off the output after 10 seconds; Load >125% ±5%: report error and turn off the output after 5 seconds | ||
| Max. Efficiency (Battery Mode) | 94%@24VDC | ||
| Charger (PV/AC) | Solar Charger Type | Dual MPPTs | |
| Max. PV Input Current / Power | 22A+22A/6kW+6kW | 1*MPPT: 27A/9KW; 2*MPPTs: 22.5A/15kW | |
| Operating Voltage Range (VDC) | 80–450 | 90–485 | |
| Max. PV Open Circuit Voltage (VDC) | 500 | ||
| Max. Charge Current (PV+AC) (A) | 160 | ||
| Battery | Nominal Battery Voltage | 51.2VDC | |
| Rated Energy | 16kWh (0.2C, 25°C) | 16076KWh | |
| Usable Energy (90% DOD) | 14.4kWh | — | |
| Max. Charge/Discharge Current | 200A/200A | ||
| Operation Voltage Range | 40Vdc–58.4Vdc | ||
| Operation Temperature | -10°C–+50°C | ||
| Interface | Reveal / Communication / Monitoring | LCD/USB/WIFI | LCD/RS485, RS232, USB, Dry Contact/WIFI |
| General Data | Ingress Protection | IP20 | |
| Operating Temperature | -10°C–50°C | ||
| Relative Humidity | 5%–95% (Non-condensing) | ||
| Storage Temperature | -15°C–60°C | ||
| Max. Operating Altitude | 4000m (Derating above 1000m) | ||
| DIMENSION | Product Size (L×W×D) | 550×245×1180 | |
| Packaging Size (L×W×D) | 630×420×1264 | ||
Safety Protection
Multiple safety protections.