| Accessories (Optional) | Technical Parameters 1250kW/3354kWh | |
|---|---|---|
| Battery Parameters | Cell Type | 3.2V/280Ah, LFP |
| Rated Voltage | 1331.2V | |
| Voltage Range | 1040–1518.4V | |
| Rated Power | 1250kW | |
| System Capacity | 3354kWh | |
| Composition | 9P416S | |
| Rated Frequency | 50Hz | |
| Charge-Discharge Rate | 0.33C | |
| System Parameters | AC Side Voltage Rating | 10kVAC |
| AC Side Wiring Mode | Three Phases and Three Lines | |
| Heat Dissipation Method | Intelligent Liquid Cooling | |
| Converter Cooling Method | Forced Air Cooling | |
| Fire Protection Scheme | Composite detector in the package (smoke, temperature, combustible gas); cabin-level combustible gas detectors; smoke sensors, temperature sensors, sound and light alarms; package spraying, cluster spraying; perfluorohexanone extinguishing agent; water firefighting | |
| Protection Level | IP54 | |
| System Communication Mode | CAN, RS485, ETHERNET, 4G | |
| Cycle Life | ≥6000 Times | |
| Product Weight | ≈35T | |
| Product Dimensions (W×D×H) | 6058×2600×2896mm | |
| Environmental Conditions | Installation Method | Outdoor Installation |
| Ambient Temperature | -20°C–55°C | |
| Humidity Range | 0–95% (Non-Condensing) | |
| Altitude | 2000M | |
Safety Protection
Multiple safety protections.